EMICON RAC 351-752 Ka
Cooling capacity kW 750,0
Absorbed power kW 219,0
EER 3,42
ESEER European 5,11
Centrifugal compressors two stage oil free
Quantity n 2
Circuits n 1
Nominal absorbed current A 349,6
Maximum absorbed current A 471,06
Axial fans
Quantity n 12
Motors power kW 23,8
Total air flow m3/h 232.800
Total air flow l/s 64.667
Nominal absorbed current A 47,4
Flooded shell and tube evaporator
Quantity n 1
Water flow rate m3/h 128,8
Water flow rate l/s 35,8
Pressure drop kPa 71
Water volume l 110
P1 Pump group
Available pressure with P1 KW 149
Motor power with P1 KW 11,0
Nominal absorbed current A 22,0
P1H Pump group
Available pressure with P1H kPa 216
Motor power with P1 KW 15,0
Nominal absorbed current A 28,5
Sound power level ISO 3744
Sound power level dB(A) 89,5
Dimensions
Lenght mm 6.690
Width mm 2.230
Height mm 2.560
Transport weight 3) kg 5.230
Power supply
Power supply V / ph / Hz 40 V / 50 Hz / 3 Ph + T
NOTES
Nominal condition referred to: air 35 °C - chilled water 7/12 °C.
3) Refrigerant charge included.
Details
RefNr:
Manufacturer: EMICON
Model: RAC 351-752 Ka
Construction Year: 2014